![]() |
Frequently
Asked Questions |
|
|
|
1. Within the DR DAS central system,
how do you specify the modem configurations for individual stations?
By default communications setting for a station are defined by the Port to which it is assigned. The default setting for baud rate and modem initialization can be overridden in the Station Setup's Baud RATE: and INIT STR: fields.
2. What modem initialization strings
should be used at the central polling system? 3. What settings are recommended for
modems used with the EnvidasFW data logger? To initialize the modem to only connect at one specific baud rate (9600) you would add "n0s37=9". This turns off auto detection and fixes the connection at 9600 baud. Other values for s37 are 8(4800), 6(2400) and 5(1200). If the modem does not support the n0s37=x commands, you can use &Nx, where 6=9600, 4=4800, 3=2400, 2=1200. Note: it is tempting to just let the modems negotiate with each other to find the highest possible communication speed. But the station devices are set for a fixed baud rate so any higher rates used by the modems serve no benefit. In fact it takes much longer for the connection to be made and failures are more frequent when you do not fix the modem connect speed. For modem communication you enter the modem communications time-out (in minutes) within the Timeout text box. For hourly data a value of 70 minutes is suggested. If after 70 minutes no communications has occurred on the port the modem is automatically reinitialized. If reinitialization fails repeatedly the EnvidasFW program will reboot the system. For internal modems this will also do a hard reset on the modem. For external modems power should be run through a relay that will open when the Envidas reboots, cycling power on the modem. Enter 0 minutes if the connection is a leased line or direct serial cable. When 0 minutes is entered the initialization string is not sent.
4. Where can I find information on
modem commands? |
|
|
|
|